Table Of Contents

Title:

Piping and Valves

Doc. No.

L-001

Annex

C

EDS

NLB1

Project: NORSOK

Company:

Rev.Date:

 15.12.97

Rev:

2

 

LINE BLINDS AND SPACERS

Spectacle blinds, paddle blanks and spacers shall be in accordance with API Standard 590 except as modified in Piping Class Sheet and this EDS-sheet.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING

MATERIAL

MODIFIC. OF

NOM. SIZE (in)

CLASS

TYPE

API 590(mm)

0.5

.75

1

1.5

2

3

4

6

8

10

12

14

16

18

20

24

30

36

150 FF

A516 gr70

Thickn(t)

5

6

6

6

7

9

10

14

16

19

22

24

27

30

32

38

46

55

 

A240 316

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S31803

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S32550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diam.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6Mo

Inside(B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

753

897

 

B265 gr2

Outside(O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

880

1045

300 FF

A516 gr70

Thickn(t)

5

6

6

8

10

13

15

20

24

29

34

37

41

46

50

60

70

85

 

A240 316

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S31830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S32550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diam.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6Mo

Inside(B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

897

 

B265 gr2

Outside(O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

949

1114

600 RTJ

 

Thickn(t)

20

24

24

24

30

34

38

46

53

60

67

72

79

88

98

115

130

150

 

A516 gr70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 316

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S31830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S32550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diam.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6Mo

Inside(B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

735

880

 

B265 gr2

Outside(O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

968

1127

900

 

Thickn(t)

25

26

26

30

38

38

42

52

61

69

79

91

100

113

122

146

180

190

 

A516 gr70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 316

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S31830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S32550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diam.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6Mo

Inside(B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

710

855

 

B265 gr2

Outside(O)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1007

1197

1500 RTJ

 

Thickn(t)

25

26

26

30

38

46

52

65

80

91

110

121

135

148

159

188

 

 

 

A516 gr70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 316

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S31830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S32550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6Mo

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B265 gr2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500 RTJ

 

Thickn(t)

30

32

32

40

45

55

66

88

106

129

147

 

 

 

 

 

 

 

 

A516 gr70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 316

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S31830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A240 S32550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6Mo

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B265 gr2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Corrosion allowance: Calculation is based on 3.0 mm corrosion allowance.

RTJ Ring type joint gasket

FF Flat face blind for raised face (RF) flanges.

(Blanks and spacers shall not be supplied with raised face).

SPIRAL WOUND GASKETS: Use blanks and spacer of FF-type where spiral wound gasket is specified.

Blanks and spacer for RTJ gaskets shall be of the Ring Joint Facing type.

Gasket surface finish shall be according to ASME B16.5 for RF blinds and spacers, but CL600 rating shall have maximum 250 micro inch finish.

Paddle blanks and spacer to be stamped "Blank" and "Spacer" respectively on both side of the handle.

Paddle blanks heavier than 20 kg shall have lifting point. (Eybolt or equivalen not to be confused with hole for visual identifcation on paddle spacer).